Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
07/06/2005 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
03/01/2005 PLUMBING - SEWER HCS CONNECT Partial Approval 1) MANHOLE #1 TO MANHOLE #5 5 PSI AIR TEST OK
2) MANHOLE #1TO MANHOLE #9 4 PSI AIR TEST OK
3) MANHOLE #4 TO MANHOLE #6 4 PSI AIR TEST OK
4) MANHOLE #6 TO SOUTH EAST BLDG #3 4 PSI AIR TEST OK
5) MANHOLE #1 VACCUM TEST OK
6) MANHOLE #2 VACCUM TEST OK
7) MANHOLE #3 VACCUM TEST OK
8) MANHOLE #4 VACCUM TEST OK
9) MANHOLE #5 VACCUM TEST OK
10) MANHOLE #6 VACCUM TEST OK
11) SEWER AIR TESTING COMPLETE OK
12) WILL NEED REVISED APPROVED PLAN FOR ADDITION OF MANHOLE #6 AND PPEQ CERTIFICATE OF COMPLIANCE
02/28/2005 PLUMBING - SEWER HCS CONNECT Partial Approval 4" HCS CONNECTION AT SOUTH WEST CORNER OK
02/24/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* MANHOLE #1 TO MANHOLE #2 4 PSI PRESSURE TEST OK.
MANHOLE #2 TO MANHOLE #3 4 PSI PRESSURE TEST OK.
MANHOLE #3 TO MANHOLE #4 4 PSI PRESSURE TEST OK.
MANHOLE #4 6" HCS LATERAL TO BUILDING #2 4 PSI TEST OK.
MANHOLE #4 6" LATERAL TO C/O 3A, 4" TO C/O RIM 44.94 TO NORTH END BLD #2. 4 PSI TEST OK
02/18/2005 PLUMBING - SEWER HCS CONNECT Cancelled IVRS - RI canceled
11/02/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/8" SEWER FROM EXISTING MANHOLE #9 TO NEW MANHOLE #1, 8" SEWER FROM MANHOLE #1 EAST TO MANHOLE #5. FROM MANHOLE #1 NORTH TO 8" SEWER TO MANHOLE #2, FROM MANHOLE #2 TO MANHOLE #3 8" SEWER, FROM LATERALS, FROM MANHOLE #4 4" HCS LATERAL EAST 100', 6" HCS LATER 76.7 NORTH, 6" HCS LATERAL 34' WEST, FROM MANHOLE #2 6" HCS LATERAL 79' MORTH EAST. FROM MANHOLE #1 8" SEWER TO MANHOLE #5 OK. 1)WILL REQUIRE AIR TEST, MANDROL, VACUUM TEST AND VERIFICATION OF GRADE, WITH PDEQ CERTIFICATION AT LATER DATE
10/19/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
10/18/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*/THERE IS A REVISED PLAN THAT SHOWS 5 NEW MANHOLES INSTEAD OF CITY APPROVED PLAN WITH 4 MANHOLES, THIS PLAN NEEDS TO BE CITY APPROVED AND ON SITE. ADDED MANHOLE IS BETWEEN #1 AND WHAT IS #2 ON 8/23/04 PLAN