Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2005 |
PLUMBING - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 01/24/2005 |
PLUMBING - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* PROVIDE HANGERS AT CORRECT INTERVALS |
| 12/14/2004 |
PLUMBING - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* H20 PIPING AIR TEST 100PSI OK PONDING CITY APPROVED REVISED PLAN. WATER TEST THRU ROOF ON WASTE + VENT OK. 1) P-4 FIXTURE WILL REQUIRE 2" P-TRAP. 2) ROP ?? ON JOB,PROVIDE REVISED CITY APPROVED DRAWING OF YOUR INSTALLATION. COVER AT YOUR OWN RISK |
| 12/13/2004 |
PLUMBING - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* |