Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/22/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)ROOF FRAME NOT PER PLAN. PLAN CALLS FOR JOIST TO BE EAST WEST BY EXISTING HOUSE BUT ARE INSTALLED NORTH SOUTH AND ARE BEARING ON FRAME WALL NOT ANCHORED PER CODE. HAVE PLAN REVISED TO AS BUILT 2)POST IS MISSING FROM PRE EXISTING SOUTH ROOM AND A SITE BUILT POST AND BEAM INSTALLED. HAVE PLAN REVISED TO AS BUILT 3)PLAN CALLS FOR 4X4 POSTS NOT DOUBLE 2X4 POSTS 4)PLAN CALLS FOR 6X8 BEAM AT 8' DOOR-PRESENTLY MO??ONARY - REFUSE PLAN 5)5/3 NOT COMPLING WITH 6)WEST DUCT WORK NOT PER PLAN-REVISE PLAN 7)NO DWV PLUMBING WATER TEST. FILL ALL TO ROOF WITH WATER 8)PLAN CALLS FOR COPPER PLUMBING PEX USE A BUILD TO PLAN OR FEVISE TO AS BUILT 9)GAS LINE MUST BE ELECTRICALLY BONDED 10)WALK IN CLOSET MISSING LIGHTS. SEE PLAN 11)COULD NOT FIND GAS PRESSURE TEST. STOPPED INSPECTION - TOO MANY ITEMS |