Permit: T04CM02431

Parcel: 10819009B


Addresses:

4798 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM02431

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :* APPROVED 1) OK TO COVER PANELS M & R EM, EM1, N 2) GROUNDS TO ANT MAST NOT FINISHED. 3) DISCON'S FOR HVAC SYSTEMS TO BE MOVED FOR CLEARANCE
03/03/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* PARTIAL OK TO CLEAR TEMP POWER WILL NOTIFY TEP
03/01/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL CLASS R FUSING AND REJECT PINS ON ALL DISCONNECTS
2) INSTALL BONDING JUMPERS IN CT ? AT LINE SIDE ENTRY
3) FINISH GROUND ROD THERMO WELDS
01/19/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* PARTIAL MENS & WOMENS RESTROOMS & SHOWERS OK TO COVER.
01/14/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/13/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :PIPE AND BOXES ON SURFACE - RESIDENTIAL SIDE