Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/APPROVED | |
| 08/17/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 3/8" ID X 18" GAS FLEX NOT ADEQUATE FOR 100,000 BTU FURNACE. SEE LISTING ON FLEX. 60 AMP CIRCUIT FROM DISCONNECT TO UNIT REQUIRES #6 WIRE. PROVIDE A FRESH AIR INTAKE ON A/C UNIT. RECALL FOR INSPECTION |