Permit: T04CM01977

Parcel: 125110580


Addresses:

3825 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/03/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/29/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) 2ND FLOOR APPEARS TO BE ROUGHED-IN OK
07/27/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) 2ND FLOOR ROUGH-IN. FIRE ALARM, LIGHTING AND OTHER ROUGH-IN WILL BE SURFACE MTD.
07/26/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK 1ST FLOOR
NO WORK PROGESS 2ND FLOOR
07/23/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 1ST FLOOR: OPEN UP WALL FOR NEW M/C CABLE-WE HAVE MISSING KO SEAL, UNSUPPORTED CABLE AND OPEN SPLICES 2) 2ND FLOOR: MISSING PLASTER RINGS 3) GROUND JUNCTION BOXES 3) SUPPORT CONDUIT ON VERTICAL RUN AND WITHIN 3' OF BOX/FITTINGS 4) USE APPROVED M/C FITTINGS 5) SUPPORT M/C CABLE WITHIN 12" OF BOXES 6) FILL UNUSED OPENING IN BOX 7) FINISH ELECTRIC 8) PLEASE PROVIDE A LETTER FROM THIS ENGINEER AUTHORIZING RING USE OF M/C CABLE