Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/29/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) 2ND FLOOR APPEARS TO BE ROUGHED-IN OK | |
| 07/27/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) 2ND FLOOR ROUGH-IN. FIRE ALARM, LIGHTING AND OTHER ROUGH-IN WILL BE SURFACE MTD. | |
| 07/26/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :OK 1ST FLOOR NO WORK PROGESS 2ND FLOOR |
|
| 07/23/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 1ST FLOOR: OPEN UP WALL FOR NEW M/C CABLE-WE HAVE MISSING KO SEAL, UNSUPPORTED CABLE AND OPEN SPLICES 2) 2ND FLOOR: MISSING PLASTER RINGS 3) GROUND JUNCTION BOXES 3) SUPPORT CONDUIT ON VERTICAL RUN AND WITHIN 3' OF BOX/FITTINGS 4) USE APPROVED M/C FITTINGS 5) SUPPORT M/C CABLE WITHIN 12" OF BOXES 6) FILL UNUSED OPENING IN BOX 7) FINISH ELECTRIC 8) PLEASE PROVIDE A LETTER FROM THIS ENGINEER AUTHORIZING RING USE OF M/C CABLE |