Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* GAS CARD ON PIPE AT TEST SETUP |
|
| 07/17/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 06/07/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1" GAS YARD PIPING W/PRESSURE TEST IS OK TO VOVER |
|
| 06/01/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* TEST HOLDING ON GAS PIPING. YARD PIPING HAS NOT BEEN PROPERLY INSTALLED. JOINTS ON METALLIC PIPING BELOW GRADE SHALL BE PRIMED W/ APPROVED GAS PIPE PRIMER BEFORE WRAPPING WITH 10 MIL. TAPE. PIPING INSIDE OF BUILDING IS NOT INSTALLED PER PLAN. A PLAN REVISION IS REQUIRED WHEN CHANGES ARE MADE. |
|
| 05/31/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS PIPING IS NOT INSTALLED PER PLAN. GAS YARD PIPING DENIED. JOINTS AND TOOL MARKS SHALL HAVE PRIMER APPLIED BEFORE WRAPPING W/10 MIL. TAPE. USE "GAS PIPE PRIMER". NOTE: URINAL NOT SHOWN ON PLAN, PIPING WAS NOT INSPECTED. FLOOR DRAIN WAS NOT INSPECTED. |