Permit: T04CM01934

Parcel: 120081020


Addresses:

4573 S 12TH AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/21/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
GAS CARD ON PIPE AT TEST SETUP
07/17/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
06/07/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1" GAS YARD PIPING W/PRESSURE TEST IS OK TO VOVER
06/01/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST HOLDING ON GAS PIPING.
YARD PIPING HAS NOT BEEN PROPERLY INSTALLED.
JOINTS ON METALLIC PIPING BELOW GRADE SHALL BE PRIMED W/ APPROVED GAS PIPE PRIMER BEFORE WRAPPING WITH
10 MIL. TAPE.
PIPING INSIDE OF BUILDING IS NOT INSTALLED PER PLAN.
A PLAN REVISION IS REQUIRED WHEN CHANGES ARE MADE.
05/31/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS PIPING IS NOT INSTALLED PER PLAN.
GAS YARD PIPING DENIED.
JOINTS AND TOOL MARKS SHALL HAVE PRIMER APPLIED BEFORE WRAPPING W/10 MIL. TAPE. USE "GAS PIPE PRIMER".
NOTE: URINAL NOT SHOWN ON PLAN, PIPING WAS NOT INSPECTED. FLOOR DRAIN WAS NOT INSPECTED.