Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 07/12/2006 | PLUMBING - YARD WTR LINE/TEST | Cancelled | ||
| 07/12/2006 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 06/22/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* - HB BEING USED W/OUT BACKFLOW PROTECTION - INSTALL VAC BREAKER. - DO NOT USE WATER FROM UNPROTECTED HB - ICE MACHINE INCORRECTLY INSTALLED. ALSO NOT ON PLAN. - ICE MACHINE HAS NO BACKFLOW PROTECTION. CONDENSATE IS CONNECTED TO DRAIN OF ICE BIN. IMMEDIATELY DISCONTINUE USE OF THIS EQUIPMENT. - URINAL INSTALLED IS NOT ON PLAN. DRAIN PIPING WAS NOT TESTED. - WATER SUPPLY IS UNDERSIZED FOR URINAL. - A 2ND HAND SINK WAS ADDED. - REMOVE FIXTURES NOT ON PLAN. - RETEST INTERMEDIATE DWV. - UNCOVER YARD WATER LINE FOR INSPECTION. - UNCOVER EXTERIOR WATER PIPING TO HB FOR INSPECTION - GAS PIPING NOT INSTALLED PER PLAN. - HAVE REVISED PLAN ON SITE FOR FUTURE INSPECTIONS OR INSTALL PER PLAN, SEE NOTES FROM PREVIOUS INSPECTIONS - GREASE TRAP IS NOT 2". PROVIDE PROPERLY SIZED GT. - DRAINAGE FITTINGS REQUIRED. WOOD SUPPORTS NOT ALLOWED. - VENT TERMINATION WITHIN 10' OF COOLER. - NOT A COMPLETE LIST OF CORRECTIONS. |