Permit: T04CM01934

Parcel: 120081020


Addresses:

4573 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/10/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/04/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
GFI RECEPTS NOT WIRED CORRECTLY -- CHECK ALL RECEPTS.
07/28/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SUPPORT DISCONNECTS ON ROOF - ALSO INSTALL ROOF JACKS FOR CONDUIT PENETRATIONS.
2. INSTALL GFI PROTECTION FOR KITCHEN AREA WHERE PERSONS IN CONTACT WITH FOOD PREP EQUIP.
STORAGE OK
PER ART. 210 NEC
07/25/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES INSP. 6/12/06 NO COMPLIANCE
07/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ONE HERE
NO MESSAGE LEFT
06/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE LADDER FOR ROOF ELECTRIC INSPECTION.
2. LABEL CIRCUIT BREAKERS IN PANEL
SOME SCREWS MISSING TO COVER
3. ALL RECEPTACLES FOR PERSONNEL TO BE GFI PROTECTED PER NEC