Permit: T04CM01767

Parcel: 124180370


Addresses:

1436 E 17TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/13/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/06/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) SUPPORT J-BOXES THAT ARE IN FREE AIR
2) LEAVE TILE OPEN UNDER BOXES FOR INSPECTION
11/04/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/ 1) RE-CALL, RISER CONDUCTORS NOT INSTALLED YET, INSPECTOR CANNOT WAIT
11/03/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/ 1) HAVE TEMP POWER FOR TEST ADDED TO PERMIT AND CALL IN INSP. ACCORDINGLY
2) INSTALL MAIN BONDING JUMPER TO NEUTRAL AT SERVICE PER 250 NEX
3) LUGS FOR GROUNDING MUST LAY FLAT ON MOUNTING SURFACE
4) SERVICE WIRING MUST BE COMPLETE PRIOR TO RELEASE OF POWER AND INSPECTION APPROVAL
11/01/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*