Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2005 | PLUMBING - SEWER HCS CONNECT | Approved | ||
| 06/16/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | 1) UNIT # 140 BLDG DRAIN TO BLDG SEWER AND CONNECTION AT SDR 35 OK. 2) CONTRACTOR TO AS BUILT INSTALLATION.3) OK TO COVER | |
| 02/09/2005 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* 1) VACUUM TEST MH #3-16 SECONDS 2) VACUUM TEST MH #2-20 SECOND 3) REVIEWED INVERTS W/ENGINEER AND PLUMBER | |
| 02/07/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) 4" SDR 35 FROM MH # 2 WEST 50' T0 WYE FITTING OK OK TO COVER | |
| 02/06/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) LOW PRESSURE AIR TEST FROM MH #1 TO MH#2 OK AIRTEST ON SECTION BETWEEN MH #2 & MH #3 OK 2) WATER TEST ON TWO 6" BRANCHES AS NOTED ON PI.O FROM MH # 3 TO SPACE #4 & 5 OK TO COVER. | |
| 02/03/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | 1) MANHOLES #2 AND 3 BASES POURED 2) 8" SDR 35 BETWEEN BASES-INSTALLED OK. OK TO COVER, SUBJECT TO VERIFICATION OF GRADE AND LOW PRESSURE AIR TEST-WITH TWO BRANCHES |
|
| 02/02/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) FROM PREVIOUS INSPECTION TO MH #2 OK TO COVER. NOTE: SECTION OF SDR 35 WITHIN ONE FOOT VERTICAL DISTANCE FROM ELECTRIC & PHONE LINE ENCASED IN CONCRETE AS PER APPROVED PLAN. 2) OK TO COVER. | |
| 02/01/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* SDR 35 FROM WALL TO 270' OK TO COVER . SUBJ TO VERIFICATION OF GRADE AND LOW PRESSURE TEST. | |
| 01/27/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* BASE FOR M-H # 1 OK APROX 39' SDR 35 INSTALLED CONTRACTOR WILL TEST AT LATER DATE & PROVIDE VERIFICATION OF VACUUM TEST REQUIRED ON ALL M-H |