Permit: T04CM00757

Parcel: 133230880

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/30/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/18/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CONDENSATE CANNOT TERMINATE INTO THE SEWER VENTS. CAN GO TO DOWNSPOUTS 2)PROVIDE FRESH AIR INTAKES AHEAD OF FILTERS, 3)USE #6 WIRE FROM DISCONNECT TO UNIT ON 5 TON UNITS. SUPPORT ELEC. DISCONNECTS.