Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/12/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK TO COVER GROUNDING 1. SUPPORTING NOT TO BE OFF OF OTHER WIRING METHODS THHN IS NOT AN APPROVED METHOD ALSO - 300.11 STATES TO BE ATTACHED AT BOTH ENDS. 2. WRITING ON PLANS |
|
| 11/29/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*SUPPORT BOXES TO GRID 410.16 AND PROVIDE A SYSMIC WIRE UP TO STRUCTURE SUPPORT FLEX TO CANS AS PER CODE PLEASE FINISH PREVIOUS ITEMS CIRCLED |
|
| 11/19/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) INSTALL EM LIGHTS AND EXIT SIGNS AS PER PLANS 2) OPEN WALLS AS DISCUSSED FOR ACCESS 3) WHERE IS CHILLER ON PLANS 4) MAINTAIN WORKING CLEARANCES IN FRONT OF SUB-PANEL 5) SUPPORT NM CABLES AS PER CODE AND WITHIN 12" OF CANS SUPPORT BOXES ABOVE CEILING 6) PLEASE PROVIDE A LETTER AUTHORIZING USE OF NM CABLE 7) FILL UNUSED OPENING IN BOXES 8) RE-CONNECT PVC CONDUIT TO FITTING-USE APPROVED FITTING 9) SERVICE IS NOT REFLECTIVE OF WORK INSTALLED 10) PLEASE REVISE AND RESTAMP |