Permit: T04CM00757

Parcel: 133230880

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/14/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/12/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK TO COVER GROUNDING
1. SUPPORTING NOT TO BE OFF OF OTHER WIRING METHODS
THHN IS NOT AN APPROVED METHOD ALSO - 300.11 STATES TO BE ATTACHED AT BOTH ENDS.
2. WRITING ON PLANS
11/29/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*SUPPORT BOXES TO GRID 410.16 AND PROVIDE A SYSMIC WIRE UP TO STRUCTURE
SUPPORT FLEX TO CANS AS PER CODE
PLEASE FINISH PREVIOUS ITEMS CIRCLED
11/19/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) INSTALL EM LIGHTS AND EXIT SIGNS AS PER PLANS
2) OPEN WALLS AS DISCUSSED FOR ACCESS
3) WHERE IS CHILLER ON PLANS
4) MAINTAIN WORKING CLEARANCES IN FRONT OF SUB-PANEL
5) SUPPORT NM CABLES AS PER CODE AND WITHIN 12" OF CANS SUPPORT BOXES ABOVE CEILING
6) PLEASE PROVIDE A LETTER AUTHORIZING USE OF NM CABLE
7) FILL UNUSED OPENING IN BOXES
8) RE-CONNECT PVC CONDUIT TO FITTING-USE APPROVED FITTING
9) SERVICE IS NOT REFLECTIVE OF WORK INSTALLED
10) PLEASE REVISE AND RESTAMP