Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/17/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) AFTER HOURS INSPECTION. DUCT SMOKE DETECTORS OPERATIONAL. OK FOR FINAL C OF O. COLLECTED $108.00 BY CHECK #1355 |
| 04/16/2004 |
MECHANICAL - FINAL |
|
Denied |
DUCT SMOKE DETECTORS NOT SHUTTING OFF EQUIPMENT. RECALL FOR INSPECTION. OK FOR TEMP C OF O |
| 04/15/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EXTEND SEWER VENT 2' ABOVE OUTSIDE AIR INTAKE. 2) FUSE ELEC. DISCONNECTS ACCORDING TO DATA PLATES ON A/C UNITS. 3) INSTALL DUCT SMOKE DETECTORS. 4) INSTALL TRANSFER GRILLS IN RESTROOM. |