Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T04CM00398
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2004 | ELECTRIC - PROGRESS | Approved | ||
06/18/2004 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :*/ CANCELLED. | |
06/11/2004 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
06/01/2004 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :*/ OK CONDUITS UNDER SLAB FOR SENSOR MATIC, 2 CASH WRAPS. | |
05/25/2004 | ELECTRIC - PROGRESS | Partial Approval | WALLS AND HARD CEILINGS FROM E TO E-2. | |
05/21/2004 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) HOME RUNS ARE DEPICTED ON PLANS AS INDIVIDUAL CONDUIT RUNS 2) YOU HAVE COMBINED HOME RUNS NOW YOU NEED TO COMPLY WITH/ART 310.15 (B) (2) DIRECTORY. WILL NEED APPROVED REVISION (ENGINEER'S LETTER) AND THE UPGRADE IN WIRE SIZE |
|
05/20/2004 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :*/ BATHROOM BAR SALES AREA EGRESS CORRIDOR WALLS APPROVED. - COMBINING HOMERUNS WILL NEED TO DERATE OR OPP PER ART. 310 NEC. |