Permit: T04CM00340

Parcel: 110102610

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
07/02/2004 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
06/24/2004 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*/ 1) BONDING JUMPER TO BE SIZED PER 250-102 AND 250.66. 2) PLEASE REUSE PLANS AS DISCUSSED.