Permit: T04CM00284

Parcel: 11007414B


Addresses:

3925 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/28/2005 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/30/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* VENTS ON CONDENSATE DRAIN LINES MUST BE DOWNSTREAM OF THE TRAP. CONDENSATE DRAINS ON REFRIGERATION CASES OK TO COVER.
03/24/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* OK TEMP C OF O. OK TO COVER PHARMACY, TELEPHONE, BREAK RM AREA. OK TO COVER.
03/23/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* NEED SEISMIC ON SUPPLY /RETURN DIFFUSERS W/HARD DUCT FEEDS
03/18/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* DUCTS ABOVE CEILING GRID, NEED STRAPS OR # 9 WIRE SEISMIC WIRE, REGISTERS TO STRUCTURE.
03/08/2005 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* NOT READY
02/23/2005 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :* NOT READY INSPECTED SUPPLY & EXHAUST IN RESTROOMS OK FOR SHEET ROCK