Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
Permit Number - T04CM00284
Inspection Description - PLUMBING - ROOF DRAINS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2005 | PLUMBING - ROOF DRAINS | Approved | ||
03/22/2005 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 10" OVER FLOW DRAINS TEST ON PIPING ONLY LEAK AT CLAMPING RINGS. ALSO CODE VIOLATION OVERFLOW TO BE 2" ABOVE HOW LOW POINT APPROX 5" NEED TO MAKE CORRECTION. I WILL NEED DIRECTION FROM YOUR ARCHITECT ON DRAIN WITH EXTRA CLAMPING RINGS AS PER INSTALLATION STANDARDS. WILL REQUIRE TEST TO DECK BEFORE APPROVAL IS GIVEN | |
03/21/2005 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* TEST ON 12" OVER FLOW OK . TEST ON 10" ROOT PLAN ONLY WILL NEED TO TEST OVER 10" OVER FLOW'S. PLEASE NOTE CODE VIOLATION ON OVER FLOW DRAIN SEE 94 APPENDIX D RAINWATER SYSTEMS. OVERFLOW DRAIN SHALL BE INSTALLED 2" ABOVE LOW POINT OF ROOT. OVERFLOW DRAIN IS APPROX 5" ABOVE LOW POINT. THIS WILL NEED TO BE CORRECTED BY FINAL |