Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
| Date |
Description |
Inspector |
Results |
Comments |
| 06/08/2005 |
PLUMBING - ROOF DRAINS |
|
Approved |
|
| 03/22/2005 |
PLUMBING - ROOF DRAINS |
|
Partial Approval |
IVRS - Inspection :* 10" OVER FLOW DRAINS TEST ON PIPING ONLY LEAK AT CLAMPING RINGS. ALSO CODE VIOLATION OVERFLOW TO BE 2" ABOVE HOW LOW POINT APPROX 5" NEED TO MAKE CORRECTION. I WILL NEED DIRECTION FROM YOUR ARCHITECT ON DRAIN WITH EXTRA CLAMPING RINGS AS PER INSTALLATION STANDARDS. WILL REQUIRE TEST TO DECK BEFORE APPROVAL IS GIVEN |
| 03/21/2005 |
PLUMBING - ROOF DRAINS |
|
Partial Approval |
IVRS - Inspection :* TEST ON 12" OVER FLOW OK . TEST ON 10" ROOT PLAN ONLY WILL NEED TO TEST OVER 10" OVER FLOW'S. PLEASE NOTE CODE VIOLATION ON OVER FLOW DRAIN SEE 94 APPENDIX D RAINWATER SYSTEMS. OVERFLOW DRAIN SHALL BE INSTALLED 2" ABOVE LOW POINT OF ROOT. OVERFLOW DRAIN IS APPROX 5" ABOVE LOW POINT. THIS WILL NEED TO BE CORRECTED BY FINAL |