Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM00284
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/28/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK LIU MAKE-UP - PLEASE VERIFY ISOLATED GROUND SYSTEM. PLANS DO ONT REFLECT A FULL SYSTEM. OK POWER FOR REFRIGERATED CASES- CHECK CONNECTIONS FOR FINAL. OK TEMP C OF O FOR STOCKING ONLY SUBJECT TO OTHER INSPECTIONS AND DETERMINATION OF STEVE LONG. 1) SUPPORT DATA CONDUIT DOWN TO FLOOR AND THIGHTEN LOOSE FITTINGS. | |
02/25/2005 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - AP canceled | |
02/25/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | OK 1" UG INTO BLD AND TO SITE LIGHTING PULL BOX | |
02/24/2005 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - AP canceled | |
02/24/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | OK FEEDERS & PANEL MAKE UP ALL PANELS EXCEPT LI-U | |
02/23/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL UNISTRUT LIGHTING CHANNEL SUSPENSION SYSTEM PER E-1 ( DETAIL 5) OK DE. CASC ? BOX W/1 SEALTIGHT WHIP FOR REF. CONTRACTOR. | |
02/22/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | OK MENS RESTROOM WALLS & HARD LIDS. OK AC UNITS ON ROOF. OK TO CLEAR TEMP POWER FOR TEST-SUBJECT TO BOND. POSTING RECEIVED GFI MAIN BRKR. TEST. | |
02/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | NO BOND AT THIS TIME. OK HARD CEILING MAIN LOBBY. OK FIRE RISER ROOM AND WEST BATHROOM OK L1D1. 1) 230. 95 TESTING TO BE AS PER MANUFACTURES INSTRUCTIONS | |
02/17/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED LETTERS OF TORQUE. OK MSB2, L1B, H1P. CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT PROCEDURES. 1) FINISH GFCI TEST AS PER 330.95 2) BOND NOT POSTED AT THIS TIME. | |
02/16/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1) WIRE & SPIRITS AREA OK. COVERED WALL FRONT. 2) 2010 PARTIAL 1" FRONT OF BLDG 15' PAST SIDEWALK. 3) TRANSFORMERS TIB & T2B OK TO COVER TERMINATION CHECKED SUPPORT RACEWAY ENTRIES ON OUTSIDE WITH 3'. 4) SALES FLOOR ABOVE CEILING OK TO CLOSE ELECT BOXES AND FIXTURES. 5) 84 CIRCUIT PANEL LID 3 OK ON HIGHT | |
02/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*1) WINE & SPIRITS ROOM COVERED WITHOUT INSPECTION -NEED DRY WALL REMOVED FOR INSPECTION. OK WALLS NORTH OF COLUMN " D" AND EAST OF COLUMN " 3" | |
02/09/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK PHARMACY 1) JUNCTION BOXES TO BE ACCESSABLE | |
02/04/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK WALLS DELI, PHOTO,CASH ROOM. OK TO CLOSE CONTINUOUS ROW FIXTURES EXCEPT POWER ??. 1) HIGHEST AVAILABLE BREAKER NOT TO BE OVER 6' 7" 380-8 (A) | |
01/26/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL ELECTRICAL RM, COMMUNICATIONS RM, OFFICE, TRAINING, SW ROOM OK EAST & WEST CANOPY WALL OK | |
01/24/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 1) MISSING PLASTER RUGS. 2) FILL UNUSED OPENINGS IN BOX. 3) FINISH CONDUIT RUNS | |
01/14/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MEET ELECTRICIAN TO DISCUSS WORKING CLEARANCES |