Permit: T04CM00284

Parcel: 11007414B


Addresses:

3925 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T04CM00284

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2005 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/09/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :* PARTIAL OK 1 POLE BASE IN FRONT OF STORE
03/07/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*NOT READY
02/16/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :* PARTIAL 1" FRONT OF BLDG 15' PAST SIDEWALK
02/02/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :* PARTIAL OK U.G TO PHARMACY DRIVE THROUGH
01/20/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :* OK 1" PVC PULL BOX OUT TO BUILDING 10' OUT FROM BUILDING 10' BACK OF BUILDING FOR FUTURE POLE. 1) SERVICE CLEARANCES TO BE AS PER 110.26
01/19/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
12/23/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3/4" AND 1" PVC FROM ED2 OUT TO EQUIPMENT
12/17/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 2-2" PVC AND 1-2 1/2" PVC ? 1 TO SUB PANELS
2) OK 3/0 TO COLUMN 3.7/E
12/15/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 5-4" PVC CONDUITS FROM OUTSIDE WALL TO INSIDE STUB UP 20' OK TO COVER
12/09/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/OK 3/0 & 2 GROUND RODS. OK 5-4" PVC SES TO XFMR. OK 5-4" PVC SES TO BLDGING. 1)MIDDLE 4" PVC AT HEATED BEND IS FLATENED OUT