Permit: T04CM00213

Parcel: 107131150

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/07/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) OK FOR SHEETROCK ON FINAL PROVIDE A DAMPER AT COOLERS A FUSE STAT AT FURNACE
12/27/2004 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/PROVIDE DAMPERS IN PLENUMS AT TOP OF FURNACE & AT EVAP. COOLERS. PROVIDE BATHROOMN EXHAUST FANS. EXTEND LOW COMBUSTION AIR TO WITHIN 12" OF FURNACE PLATFORMS. REPLACE WATER HEATER VENT W/DOUBLE WALL & PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES. PROVIDE HIGH COMBUSTION AIR FOR WATER HEATER. HAVE PLUMBING INTERMEDIATE & FINAL ADDED TO PERMIT & ALSO GAS PRESSURE TEST. PROVIDE AN ENCLOSURE FOR WATER HEATER.