Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/26/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. OK FOR GAS MECHANICAL INSPECTOR TO LEAVE GAS CARD. |
| 12/30/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) INSTALL 90o ELL ON T&P TERMINUS. 2) SINGLE WALL VENT CONNECTOR REQUIRES 6" OF CLEARANCE FROM COMBUSTABLES. NOTE: DOUBLE WALL REQUIRES ONLY 1". 3) USE METAL BACK TAPE, NOT DUCT TAPE. SUPPORT VENT SYSTEM. |
| 12/17/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) WTR HTR NOT READY. 2) GAS PRESSURE TEST OK. |
| 12/05/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ OWNER HAS SEVERAL CORRECTIONS TO MAKE INCLUDING PERMITS FOR WTR HTR AND ROOFTOP GAS PACK. |