Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/03/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ INSPECTED AM, LEFT INSTRUCTIONS FOR CORRECTION. REINSPECTED AT 1:00 PM - CORRECTIONS MADE - OK FOR GAS. METER IS ON. OK TO ACTIVATE. |
| 10/22/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE PROVIDE GAS ISOMETRIC SHOWING DEVELOPED LENGTH AND BTU CONSUMPTION. 2) PLEASE INSTALL ALL PIPING AND MAKE ALL CONNECTIONS IN ORDER TO FINALIZE INSPECTION. |
| 10/20/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PLASTIC PIPING SHALL HAVE MINIMUM 18" OF COVER. 2) PIPING OVER 14" WATER COLUMN IN PRESSURE SHALL BE TESTED AT 60 PSI. THIS MUST NOT BE A COMPLETE LIST |