Permit: T03PL01751

Parcel: 11516019K


Addresses:

1365 W GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03PL01751

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ INSPECTED AM, LEFT INSTRUCTIONS FOR CORRECTION. REINSPECTED AT 1:00 PM - CORRECTIONS MADE - OK FOR GAS. METER IS ON. OK TO ACTIVATE.
10/22/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE PROVIDE GAS ISOMETRIC SHOWING DEVELOPED LENGTH AND BTU CONSUMPTION. 2) PLEASE INSTALL ALL PIPING AND MAKE ALL CONNECTIONS IN ORDER TO FINALIZE INSPECTION.
10/20/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) PLASTIC PIPING SHALL HAVE MINIMUM 18" OF COVER. 2) PIPING OVER 14" WATER COLUMN IN PRESSURE SHALL BE TESTED AT 60 PSI. THIS MUST NOT BE A COMPLETE LIST