Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T03PL00677
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2003 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
| 04/13/2003 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*PLEASE CALL IN ALL REQUIRED INSPECTIONS AT THE SAME TIME. 2.) GAS PIPING OK PRESSURE TEST OK PROVIDE ALL CONNECTIONS FOR FINAL 3.) BOOT LEGGED WATER HEATER HAS SOME CORRECTION TO MEET MINIMUM INSTALLATION STANDARD. 1.) PVC DRAIN ON T & P RELIEF VALVE NOT APPROVED. 2.) T & P RELIEF DRAIN TO TERMINATE AT AN APPROVD LOCATION. 3.) OPEN VENT AT LAUNDRY SINK IS INSANITARY. ASK PLUMBER ABOUT AIR ADMITTANCE VALVE. 4.) WATER HEATER VENT SYSTEM NOT APPROVED. 5.) INSTALL A USABLE VALVE AT COLD WATER INLET TO W/H. |