Permit: T03PL00372

Parcel: 140430130

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
05/12/2003 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection 0000*GAS PRESSURE TEST 1" EAST MED PRESSURE FOR AIR HANDLER RM #1 IS OK @ 60LB TEST
2.) BOTH BACKFLOW PREVENTERS AND METER CONNECTION IS OK.
05/07/2003 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*
05/05/2003 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection 0000*1.) YARD WATER LINE FROM METER LOCATION TO BLDG. SERVICE IS OK
2.) MUST PROVIDE AIR TEST ON SYSTEM 60LBS MIN.
05/01/2003 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*
1.) MUST EXPOSE ALL JOINTS AND PARTIAL RUN OF PVC PIPE.
2.) CAN NOT LOCATE PVC SCH 40 PIPE UNDER THE STRUCTURE SEE SECTION: 604.1 94 UPC.
3.) MUST PROVIDE AIR TEST OR METERED PRESSURE ON SYSTEM @ TIME OF INSPECTION.
04/22/2003 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0999*1.) MUST EXPOSE ALL JOINTS IN SYSTEM AND PROVIDE AIR PRESSURE TEST @ TIME OF INSPECTION.
2.) NOTE: TRAP PRIMER LOOP & CONNECTION TO FLOOR SINK OK IN MECH RMS.