Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T03PL00372
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2003 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection 0000*GAS PRESSURE TEST 1" EAST MED PRESSURE FOR AIR HANDLER RM #1 IS OK @ 60LB TEST 2.) BOTH BACKFLOW PREVENTERS AND METER CONNECTION IS OK. |
|
05/07/2003 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection 0000* | |
05/05/2003 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection 0000*1.) YARD WATER LINE FROM METER LOCATION TO BLDG. SERVICE IS OK 2.) MUST PROVIDE AIR TEST ON SYSTEM 60LBS MIN. |
|
05/01/2003 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999* 1.) MUST EXPOSE ALL JOINTS AND PARTIAL RUN OF PVC PIPE. 2.) CAN NOT LOCATE PVC SCH 40 PIPE UNDER THE STRUCTURE SEE SECTION: 604.1 94 UPC. 3.) MUST PROVIDE AIR TEST OR METERED PRESSURE ON SYSTEM @ TIME OF INSPECTION. |
|
04/22/2003 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection 0999*1.) MUST EXPOSE ALL JOINTS IN SYSTEM AND PROVIDE AIR PRESSURE TEST @ TIME OF INSPECTION. 2.) NOTE: TRAP PRIMER LOOP & CONNECTION TO FLOOR SINK OK IN MECH RMS. |