Permit: T03OT01426

Parcel: 125121110

Inspection Status: Approved

Inspection History: SIGN ELECTRIC

Permit Number - T03OT01426

Inspection Description - SIGN ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2003 SIGN ELECTRIC Approved IVRS - Inspection 0000*
10/01/2003 SIGN ELECTRIC Partial Approval IVRS - Inspection 0000*/ 1) SIGN CIRCUIT NEED A LOCKOUT-DISCONNECTING MEANS NOT IN SIGHT 600.6 2) BOND JUNCTION BOX AND TRANSFORMER ENCLOSURES AND SIGN LETTERS WITH APPROVED METHOD-SHEET METAL AND DRYWALL SCREWS NOT ALLOWED 3) TIGHTEN CABLE CONNECTORS TO MAINTAIN GROUNDING 4) SIGN NEEDS LISTING AND 600.3 5) PROTECT PRIMARY 120V CIRCUIT TO SWITCH OR MOVE TO OUTSIDE OF TRANSFORMER ENCLOSURE 6) BOOT CONNECTOR CANNOT BE CUT TO MODIFY
08/18/2003 SIGN ELECTRIC Not ready for Inspection IVRS - Inspection 0000*/ PLEASE RECALL
08/18/2003 SIGN ELECTRIC Partial Approval