Permit: T03EL02199

Parcel: 122180640


Addresses:

1613 N WINSTEL BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) A GAS BOND IS NEEDED PER CODE 250.104 2) A CHASE NIPPLE IS NOT AN APPROVED FITTING FOR USE WITH A LB 3) PLEASE CORRECTLY LABEL BREAKER AS SUB PANEL 4) HAVE RANGE CIRCUIT ADDED TO PERMIT AND PLEASE PROVIDE ACCESS FOR INSPECTION