Permit: T03EL00393

Parcel: 12213035B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
05/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* MEET WITH CONTRACTOR DISCUSS ENTRY SYSTEM.
04/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
04/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*BONDING JUMPER TO BE SIZED PER 250-66.
2.) WE STILL NEED REVISE PLANS.
A PERMIT WITH PLANS FO R BATTERY INSTALLATION WILL NEED T0 BE OBTAINED WITHIN 30 DAY.
04/01/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
REPAIR BROKEN BARRIER IN METER SOCKET.
2.) A BONDING DEVICE AT SERVICE NIPPLE 250-94.
3.) FUSES TO BE VERIFY FOR USE OF FRN AT SERVICE
4.) PLEASE PROVIDE ORIGINAL PLAN FOR TENNENT BUILD OUT TO VERIFY EXISTING. WE HAVE PROBLEMS WITH INSTALLATION AT SUBPANEL AREA. THERE IS A BATTERY RACK AND SYSTEM THAT HAS VIOLATIONS.
5.) EXISTING SERVICE FEED HAS 1 SET OF 4 500MCM TO FEED.
GUTTER.PLEASE VERIFY LOADS OF EXISTING SERVICES.
6.) FINISH CONNECTIONS OF EXISTING CIRCUITS TO SUBPANEL.
7.) CONTRACTORS L-11 LICENSED IS AS PER REGISTRAR OF CONTRACTOR.