Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM05851
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/20/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/20/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ NEED TO SEE CLOSET FLANGES. | |
04/19/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ WOOD SHIMS ARE NOT APPROVED COPPER SUPPORTS. | |
04/16/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
04/14/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO COVER ALL AREAS. 2) NEED TO SEE CLOSET FLANGES. | |
04/13/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK-TO COVER WALLS EXCEPT WOMEN'S RESTROOM 2) SUBJECT TO REVISED APPROVED PLAN | |
04/09/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
04/07/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ PLAN DRAWN AND APPROVED IN ERROR. YOU MAY NOT REDUCE 4" TO 3" THEN INCREASE IT BACK TO 4" - CONSIDERED AN OBSTRUCTION. |