Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2004 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 04/09/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/08/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/09/2004 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) REVISED PLAN ON SITE - HOWEVER STILL INCOMPLETE. COMMERCIAL WORK REQUIRES COMPLETE ISOMETRIC DRAWINGS WHICH WERE NOT INCLUDED WITH THE REVISED PLAN. HAVE ON SITE BY NEXT INSPECTION. 2) ABS DWV UNDERGROUND OK WITH ONE EXCEPTION: W.C. WASTE 4" X 3" THEN BACK TO 4" CONSIDERED AN OBSTRUCTION - NO ISO AVAILABLE. 3) OK TO COVER ALL OTHER AREAS. |
| 03/08/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 02/13/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
1) NOT INSTALLED AS PER APPROVED PLAN. 2) ALSO PLEASE PROVIDE ISOMETRIC DRAWING AS REQUIRED BY THE CITY OF TUCSON. 3) PLEASE PROVIDE ALL SIZES OF PIPE. |