Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM05851
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2004 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
04/09/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* | |
04/08/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* | |
03/09/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) REVISED PLAN ON SITE - HOWEVER STILL INCOMPLETE. COMMERCIAL WORK REQUIRES COMPLETE ISOMETRIC DRAWINGS WHICH WERE NOT INCLUDED WITH THE REVISED PLAN. HAVE ON SITE BY NEXT INSPECTION. 2) ABS DWV UNDERGROUND OK WITH ONE EXCEPTION: W.C. WASTE 4" X 3" THEN BACK TO 4" CONSIDERED AN OBSTRUCTION - NO ISO AVAILABLE. 3) OK TO COVER ALL OTHER AREAS. | |
03/08/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000* | |
02/13/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | 1) NOT INSTALLED AS PER APPROVED PLAN. 2) ALSO PLEASE PROVIDE ISOMETRIC DRAWING AS REQUIRED BY THE CITY OF TUCSON. 3) PLEASE PROVIDE ALL SIZES OF PIPE. |