Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM05839
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2004 | MECHANICAL - FINAL | Approved | ||
03/12/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ CONFIRMED DUCT SMOKE DETECTOR OPERATIONAL. CONNECT CONDENSATE TO A/C UNIT. RETURN AIR DOOR ON A/C UNIT DOES NOT FIT. | |
03/11/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) ELEC. DISCONNECT REQUIRES 30 AMP FUSES. 2) INSTALL CONDENSATE. 3) PERMANENTLY IDENTIFY EQUIPMENT ON ROOF. 4) CONNECT BATHROOM EXHAUST DUCT. 5) CONNECT LINE VOLTAGE TO DUCT SMOKE DETECTOR. OK FOR CEILING TILE. |