Permit: T03CM05445

Parcel: 136070060


Addresses:

9252 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/01/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/ 1) OK FOR FINAL C OF O
10/28/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/UNIT DATA PLATE MARKED INCORRECTLY. THERE IS NO HEAT STRIP. FUSE DISCONNECTS ACCORDINGLY. RECALL FOR INSPECTION
10/19/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)A/C UNITS NOT PROPERLY FUSED. 2)MARK UNIT DATA PLATES W/PROPER HEAT KIT INSTALLED & FUSE ACCORDINGLY 3)USE PROPER FITTINGS TO SECURE ELEC. CONDUIT TO A/C-8. 4)PROVIDE THE GREASE CUP ON EXHAUST FAN ON ROOF-SECURE ELEC. CONDUIT. 5)NEED TO SEE EXHAUST FAN RUNNING
09/27/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*CLEARANCES TO TYPE I HOOD NOT TO CODE. SEE SECTION 507.19 2003 IMC. FINISH WORK ON ROOF