Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* APPROVED OK FOR FINAL | |
| 03/07/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SECURE ELEC. DISCONNECTS. DO NOT USE WHITE WIRE FOR LINE VOLTAGE. TAPE BOTH ENDS BLACK. SUPPORT GAS PIPE. 3/8" ID GAS FLEX NOT ADEQUATE FOR 100,000 BTU. PROVIDE ROOF JACKS AT ROOF PENETRATIONS. USE FULL LENGTH 4X4 SLEEPERS TO SUPPORT A/C UNITS. |