Permit: T03CM05167

Parcel: 128030840


Addresses:

5601 E 12TH ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/01/2005 FRAMING Approved IVRS - Inspection :*
08/26/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
08/25/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STAIRS DO NOT MEET THE MIN HEAD ROOM REQ'D OF 6'-8"
06/06/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STAIRS DO NOT MEET THE MINIMUM HEAD ROOM REQUIRED OF 6'-8"
2) RISER HEIGHT DIFFERENTIALS EXCEED 3/8"-ALMOST 2"
3) OK TO INSULATE AND ROCK ALL BUT STAIR AREA
05/11/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BANG PLATE TPR DRAIN AND 1" CLEARANCE TO FLUE
2) FHA STRAP ABS AT BOTTOM PLATE IN EAST BATH AND TOP PLATE IN W. BATH
3) BANG PLATE WIRES OVER FRONT DOOR
4) GET FIX FOR LACK OF SPACE FOR A/C SECONDARY CONDENSATE PANS (2)
5) IMPROVE TREAD BRACING AT BOTTOM OF STAIRS
6) 2003 IRC-SEC R311.5.3.2 WINDER TREADS SHALL HAVE A MINIMUM TREAD DEPTH OF 10" MEASURED AT AT PAINT 12" FROM THE NARROWER END OF TREAD
7) NEED OUTLET AT TOP OF STAIRS WITHIN 6' OF DOOR
8) RENAIL TC CLIPS
9) SHIM HEADERS WHERE NEEDED
10) SECURE DUCT IN MASTER TOILET
11) SECURE 4 GANG BOX ON STAIRS
05/06/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NEED MESH COMPLETE FOR INTERMEDIATES