Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/26/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/25/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STAIRS DO NOT MEET THE MIN HEAD ROOM REQ'D OF 6'-8" |
|
| 06/06/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STAIRS DO NOT MEET THE MINIMUM HEAD ROOM REQUIRED OF 6'-8" 2) RISER HEIGHT DIFFERENTIALS EXCEED 3/8"-ALMOST 2" 3) OK TO INSULATE AND ROCK ALL BUT STAIR AREA |
|
| 05/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BANG PLATE TPR DRAIN AND 1" CLEARANCE TO FLUE 2) FHA STRAP ABS AT BOTTOM PLATE IN EAST BATH AND TOP PLATE IN W. BATH 3) BANG PLATE WIRES OVER FRONT DOOR 4) GET FIX FOR LACK OF SPACE FOR A/C SECONDARY CONDENSATE PANS (2) 5) IMPROVE TREAD BRACING AT BOTTOM OF STAIRS 6) 2003 IRC-SEC R311.5.3.2 WINDER TREADS SHALL HAVE A MINIMUM TREAD DEPTH OF 10" MEASURED AT AT PAINT 12" FROM THE NARROWER END OF TREAD 7) NEED OUTLET AT TOP OF STAIRS WITHIN 6' OF DOOR 8) RENAIL TC CLIPS 9) SHIM HEADERS WHERE NEEDED 10) SECURE DUCT IN MASTER TOILET 11) SECURE 4 GANG BOX ON STAIRS |
|
| 05/06/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NEED MESH COMPLETE FOR INTERMEDIATES |