Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/18/2003 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* 1) POST CORRECT UNIT # OVER DOOR (161) @0 PROVIDE APPROVED C/O INSP |
| 11/14/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* SOUTH WALL OF CLEANERS TO DOOR |
| 11/13/2003 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999* FIRE BARRIERS REQUIRE SCREWS 12" OC IN FIELD AND 8" OC AT PERIMETERS. WHAT I CAN SEE FROM HOLE CUT IN BOTTOM DOES NOT COMPLY. PLACE FASTNERS 12" OC CLEANER SIDE ENTIRE WALL. PLACE FASTNERS 12" OC ABOVE CARD WALL ON MEMORY SIDE. |
| 11/10/2003 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999* 1) SCREWS FOR 1 HOUR BARRIER TO BE 8" OC PERIMETER AND 12" OC IN FIELD. 2) PENETRATIONS ON BOTH SIDES OF WALL REQUIRE FIRE STOP. |