Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2004 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 02/19/2004 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999*/ 1) GAPS WIDER THAN 1/4" NOT ALLOWED SEE GA-216 2) REPAIRING OF GAPS WITH METAL FLASHING NOT ALLOWED. SEE GA-216 3) WALLS DRIVEN TO DEEPLY IN BYPSUM SHEAR PANELS PAPER BROKEN REPLACE PANELS 4) #5 SHEAR WALL NOT NAILED AT TOP PLATE AT FURNACE AND BEDROOM |
| 02/17/2004 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999*/ 1) NOT READY. CHECK PREVIOUS AND COMPLY |
| 02/11/2004 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0950*STOPPED INSPECTION; TOO MANY ITEMS; NEXT FAILURE WILL BE CHARGED REFEE - 1) GAPS WIDER THAN 1/4" NOT ALLOWED 2) SHEAR WALL 5 DAMAGED. REPLACE DRYWALL 3) NAILS DRIVEN TOO DEEP; BROKEN PAPER; REPLACE DRYWALL 4) SHEAR WALL NOT NAILED AT FURNACE PLATFORM 5) SHEAR WALL 4 REQUIRES 5/8" DRYWALL 6) SHEAR WALL PANELS LESS THAN 9 FT MUST BE VERTICAL |
| 02/09/2004 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0950*/ 1) NOT COMPLETE ENOUGH TO INSPECT |