Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/27/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WATER EVERYWHER ON PLUMBING AND FLOOR UNABLE TO INSPECT. DRY OUT AND RE-TEST 2) ITEM 3 FROM 12/30/03 NOT COMPLIED WITH. ALSO FAILED 1/26/04. DOES NOT COMPLY WITH UPC 803. REFEE |
| 01/26/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) NO DWV WATER TEST AS REQUIRED BY UPC 712.2 2) NO POTABLE WATER TEST 3) 8 EACH 90 DEGREE BONDS IN A/C CONDENSATE LINE WITHOUT MAXIMUM ALLOWED 135 DEGREE OF CHANGE WITHOUT CLEANOUTS |
| 12/30/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO DWV WATER TEST PER UPC 712.2 2) 3 PT BEARING TRUSSES NOT BEARING MID POINT 3) 8 90 DEGREE BENDS IN A/C CONDENSATE NO MORE THAN 2-90 DEGREE BENDS ALLOWED. COMPLY OR PROVIDE ENGINEERS APPROVED DESIGN 4) WIRES TRAPPED AT FIRE BLOCK 5) NAIL PROTECT WIRES WITHING 1 1/4" OF STUD SURFACE 6) SEAL VAPOR BARRIER PENETRATIONS 7) TIE INTERIOR BEARING WALL TO EXTERIOR WALLS 8) CUT OVERSIZE TRUSS SHIMS 9) FIRE STOP MINIMUM 1" 2-LAYERS 1/2" 10) NO POTABLE TEST |