Permit: T03CM04959

Parcel: 138242870

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/30/2004 FRAMING Approved IVRS - Inspection 0000*
01/27/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) WATER EVERYWHER ON PLUMBING AND FLOOR UNABLE TO INSPECT. DRY OUT AND RE-TEST 2) ITEM 3 FROM 12/30/03 NOT COMPLIED WITH. ALSO FAILED 1/26/04. DOES NOT COMPLY WITH UPC 803. REFEE
01/26/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) NO DWV WATER TEST AS REQUIRED BY UPC 712.2 2) NO POTABLE WATER TEST 3) 8 EACH 90 DEGREE BONDS IN A/C CONDENSATE LINE WITHOUT MAXIMUM ALLOWED 135 DEGREE OF CHANGE WITHOUT CLEANOUTS
12/30/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) NO DWV WATER TEST PER UPC 712.2 2) 3 PT BEARING TRUSSES NOT BEARING MID POINT 3) 8 90 DEGREE BENDS IN A/C CONDENSATE NO MORE THAN 2-90 DEGREE BENDS ALLOWED. COMPLY OR PROVIDE ENGINEERS APPROVED DESIGN 4) WIRES TRAPPED AT FIRE BLOCK 5) NAIL PROTECT WIRES WITHING 1 1/4" OF STUD SURFACE 6) SEAL VAPOR BARRIER PENETRATIONS 7) TIE INTERIOR BEARING WALL TO EXTERIOR WALLS 8) CUT OVERSIZE TRUSS SHIMS 9) FIRE STOP MINIMUM 1" 2-LAYERS 1/2" 10) NO POTABLE TEST