Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM04756
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 12/05/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ ALL CORRECTIONS MADE EXCEPT RPB FOR BOTTLE WASHER. | |
| 12/04/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PLEASE INSTALL CLEAN OUTS PER PLAN ON ALL DRAINAGE PIPING. 2) PROVIDE C/O COVER IN R/O ROOM. 3) ICE MACHINE DRAINAGE SHALL BE SEPERATE. 4) ICE MACHINE REQUIRES BACKFLOW PROTECTION OR 1" AIR GAP ON H2O INLET. 5) BOTTLE WASHER REQUIRES BACKFLOW PROTECTION FOR SUBMERGED INLET ON H2O. |