Permit: T03CM04686

Parcel: 141148180

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T03CM04686

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
02/19/2004 MECHANICAL - HOODS Approved
02/09/2004 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*/ 1) BATHROOM EXHAUST REQUIRES 6" DUCT NOT 4" 2) PROVIDE A CLEANOUT ON KITCHEN EXHAUST DUCT 3) INSTALL FIRE WRAP PER MANUFACTURERS INSTRUCTIONS 4) OK FOR CEILING TILES 5) EXTEND WATER HEATER VENT 2' ABOVE WALL ON ROOF 6) EXTEND KITCHEN EXHAUST TO TOP OF WALL
02/02/2004 MECHANICAL - HOODS Partial Approval IVRS - Inspection 0000*