Permit: T03CM04588

Parcel: 13505149M

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
11/14/2003 PLUMBING - PROGRESS Approved IVRS - Inspection 0000*
11/03/2003 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection 0000*/1) WATER HEATER VENT PIPING SHALL BE SUPPORTED BY APPROVED TYPE MATERIAL. 2) CONTRACTOR TO CHECK T&P RELIEF VALVE ON WATER HEATER, AND IT SHALL GRAVITY DRAIN TO DAYLIGHT. 3) WATER HEATER IN UNISEX RESTROOM TO HAVE T&P TO DAYLIGHT.
10/30/2003 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection 0000*/ 1) STOVE PERM CAP IS OK TO COVER. 2) WATER HEATER VENT IS NOT CORRECT. 3) T&P DRAIN SHALL GRAVITY DRAIN TO DAYLIGHT.
10/09/2003 PLUMBING - PROGRESS Denied IVRS - Inspection 0999*/ 1) PLEASE HAVE PLUMBING CONTRACTOR AND OWNER PRESENT AT NEXT INSPECTION. 2) PLEASE UNCOVER ALL WORK THAT HAS BEEN DONE SO IT IS READILY AVAILABLE TO BE SEEN AT THIS TIME OF INSPECTION.