Permit: T03CM04529

Parcel: 11703069A


Addresses:

830 N ARIZONA AV


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM04529

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/28/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/26/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) WET DIRT AT CLEANOUTS ON NORTH SIDE 2) NO WATER IN 10' STACK 3) SOUTH ABS DOES NOT MATCH PLAN
04/29/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection NO PLANS ON SITE, CALLED DAVID. PLANS ARE INSIDE THE BLDG IT'S LOCKED, HE SAID HE COULDN'T COME OVER TO OPEN DOOR, WILL RECALL 2) INCORRECT FITTINGS AT DOUBLE COMBO CLEANOUTS. YOU NEED TO CHANGE OUT THE COMBO TO A LONG SWEEP 90 DEGREE, INSTALL A 3 X 3 X 2 COMBO. ATTACHED TO HORIZONTAL DRAIN LINE, SOUTH OF 90 DEGREE. YOU WILL NOT BE ABLE TO SNAKE THRU. C.O. THE WAY OYOU HAVE IT SET UP
04/26/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :
See detailed listing on site.| 999*/ 1) 30 LF OF 3' ABS OK TO COVER LEAVE STACK AT SOUTH END AND 1 FEET FROM NORTH COMBO EXPOSED EAST WEST DRAIN ON NORTH SIDE OF HOUSE FROM N.E. CORNER OF EXISTING TO SEWER CONNECTION OK TO COVER. LAUNDRY AND BATHROOM PLUMBING AT EACH END OF DRAIN NOT INSTALLED