Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/18/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 02/12/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MAINTAIN WORKING CLEARANCE AS DISCUSSED ON PREVIOUS INSPECTIONS. 2) FINISH GAS BOND. 3) PLEASE VERIFY LISTING FOR CORD CAP TO M/C RELIEF CONNECTOR. 4) JUNCTION BOX COVERS TO BE ACCESSABLE. 5) INSTALL RELOC END CAPS AND SUPPORT AS PER M/C CODE 334 AND 604. |
| 01/23/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ OK ABOVE CEILING, EXCEPT FOR WATER HEATER INSTALL. COMPLETE INSTALL. OK TEMP C OF O FOR STOCKING |
| 01/20/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) TEMP C OF O 2) PROTECT SEAL TITE FROM SHARP METAL EDGES 3) MAINTAIN WORKING CLEARANCE AT A/C DISCONNECTS 4) PROVIDE LABEL SERVICE MAIN DISCONNECT AS DISCUSSED 5) FINISH ELECTRICAL INSTALLATION 6) OK GUTTERS PER 374.5 7) OK FOR FURNITURE ONLY- NO STOCKING-NO OCCUPANCY |