Permit: T03CM04475

Parcel: 13322471B


Addresses:

7255 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/18/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
02/12/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) MAINTAIN WORKING CLEARANCE AS DISCUSSED ON PREVIOUS INSPECTIONS. 2) FINISH GAS BOND. 3) PLEASE VERIFY LISTING FOR CORD CAP TO M/C RELIEF CONNECTOR. 4) JUNCTION BOX COVERS TO BE ACCESSABLE. 5) INSTALL RELOC END CAPS AND SUPPORT AS PER M/C CODE 334 AND 604.
01/23/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ OK ABOVE CEILING, EXCEPT FOR WATER HEATER INSTALL. COMPLETE INSTALL. OK TEMP C OF O FOR STOCKING
01/20/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) TEMP C OF O 2) PROTECT SEAL TITE FROM SHARP METAL EDGES 3) MAINTAIN WORKING CLEARANCE AT A/C DISCONNECTS 4) PROVIDE LABEL SERVICE MAIN DISCONNECT AS DISCUSSED 5) FINISH ELECTRICAL INSTALLATION 6) OK GUTTERS PER 374.5 7) OK FOR FURNITURE ONLY- NO STOCKING-NO OCCUPANCY