Permit: T03CM04475

Parcel: 13322471B


Addresses:

7255 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/12/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
01/09/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ MAIN 8X8 GUTTER ABOVE PANELS IN ELECT ROOM CONTAIN WAY OVER 30 CURRENT CARRYING CONDUCTORS REQUIRING CONDUCTORS [OVER 41] TO BE LIMITED TO 35% - SEVERAL A/C UNITS FED WITH #10 [40 AMPS] WOULD HAVE TO BE DERATED TO 15 AMPS - UNITS ALLOW ONLY 20 A CB AT PANELS, 30 AMP CBS SENT WITH PANELS, PHYSICALLY TOO DIFFICULT TO INSTALL BARRIERS IN 8X8 GUTTERS.
01/07/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) APPLY 374.5 TO GUTTERS
12/10/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) BONDING JUMPERS TO BE AS PER 250.102 AND 250.66 2) OK WALLS ? AND BELOW 3) OK TO CLEAR-CLEAR AS SERVICE UPGRADE. NOTE: BOND IS NOT REQUIRED SERVICE IS EXISTING AND CURRENTLY ENERGIZED-WILL JUST BE UPGRADED
12/09/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) AREAS COVERED IN SHEET ROCK WITHOUT INSPECTION TO BE REMOVED FOR INSPECTION
11/17/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
11/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK WALL S ROOM 105-111, EXTERIOR WHEREHOUSE NORTH EAST. OK2-4" 800 AMP DISCONNECT TO GUTTER
11/04/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR
10/31/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK BOXES IN EXTERIOR WALL, SHOW FLOOR