Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/12/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 01/09/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ MAIN 8X8 GUTTER ABOVE PANELS IN ELECT ROOM CONTAIN WAY OVER 30 CURRENT CARRYING CONDUCTORS REQUIRING CONDUCTORS [OVER 41] TO BE LIMITED TO 35% - SEVERAL A/C UNITS FED WITH #10 [40 AMPS] WOULD HAVE TO BE DERATED TO 15 AMPS - UNITS ALLOW ONLY 20 A CB AT PANELS, 30 AMP CBS SENT WITH PANELS, PHYSICALLY TOO DIFFICULT TO INSTALL BARRIERS IN 8X8 GUTTERS. |
| 01/07/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) APPLY 374.5 TO GUTTERS |
| 12/10/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) BONDING JUMPERS TO BE AS PER 250.102 AND 250.66 2) OK WALLS ? AND BELOW 3) OK TO CLEAR-CLEAR AS SERVICE UPGRADE. NOTE: BOND IS NOT REQUIRED SERVICE IS EXISTING AND CURRENTLY ENERGIZED-WILL JUST BE UPGRADED |
| 12/09/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) AREAS COVERED IN SHEET ROCK WITHOUT INSPECTION TO BE REMOVED FOR INSPECTION |
| 11/17/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/14/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* OK WALL S ROOM 105-111, EXTERIOR WHEREHOUSE NORTH EAST. OK2-4" 800 AMP DISCONNECT TO GUTTER |
| 11/04/2003 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR |
| 10/31/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK BOXES IN EXTERIOR WALL, SHOW FLOOR |