Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM04472
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/01/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
08/31/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/28/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/25/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. REDLINE DRAWING FOR WATER PIPING & HOSE BIBBS 2. RPA FOR IRRIGATION NEEDS TO BE PROVIDED 3. PROVIDE ALL CERTIFICATION OF RPA'S |
|
08/17/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - REMOVE WC'S FOR CLOSET FLANGE INSP. FLANGES SHALL BE FASTENED TO FLOOR. - DOMESTIC WATER SUPPLY NOT PER PLAN. - 4" CW REQUIRED TO 3" BRANCH - RPA REQUIRED PER IRRIGATION SUPPLY. - PROVIDE CERTIFICATION OF RPA - COOLER DRAIN PIPING NOT SIZED PER PLAN. - ALSO PROVIDE 1/8" PER SLOPE AND PROVIDE TEST. - PROVIDE SUPPORT AT 6' INTERVALS. - SECURE MOP SINK FAUCET. - REMOVE COVER OF DF FOR INSPECTION. - SUPPORT EXP. TANK W/PIPE SUPPORT MATERIAL. - 3/4 TO 1 REDUCTION AT WH DRAIN PAN IS IMPROPER USE OF FITTINGS ALSO DRAIN LINES ARE NOT TO REDUCE IN RUN. - PROVE CLEANOUT PLUGS LISTED TO RECEIVE SCREW FROM C/O COVER |