Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2006 | PLUMBING - INTERMEDIATE | Approved | ||
| 05/16/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER PIPING TYPE L COPPER W/100 PSI TEST - OK DWV TO JUST BELOW ROOF W/WATER TEST - OK PROVIDE TEST ON COOLER DRAIN LINE, OK TO COVER WALLS, TEST CAN BE OBSERVED LATER. CLOSET FLANGES NOT YET INSTALLED. MOP SINK NOT INSTALLED. |
|
| 05/12/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WATER PIPING NOT INSTALLED PER PLAN 1. UNDERSIZED 2. INSTALL WHA URINAL WASTE OUT - LOT SHALL BE A DRAINAGE FITTING. A CLEAN OUT TEE IS NOT. ALSO FEMALE PLASTIC THREADS SHOULD NOT BE CONCEALED. A MALE ADAPTER WOULD BE THE PREFERRED THREAD CONNECTION. HORIZONTAL CHANGES OF DIRECTION ON TRAP ARMS SHALL BE WYE PATTERN SWEEPS SUPPORT OVERHEAD HORIZONTAL ABS AT EACH END AND NOT TO EXCEED 4' RETEST, RECALL FOR INSPECTION. |