Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM04472

Parcel: 14027041A


Addresses:

6151 S TUCSON BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM04472

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) BLDG LOCKED, COULD NOT RETRIEVE MESSAGE, IVR SYSTEM DOWN
2) RECALL INSPECTION-PLEASE HAVE ELECTRICAL CONTRACTOR ON SITE
10/31/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
EM LIGHT MISSING ON NORTH END
SEE NOTES INSP. 10/6/06
10/20/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/06/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LETTER NOT ADDRESSING FIELD INSTALLATION BY CONTR. CIRCUITING NOT PER PLAN.
2. FINAL SUBJECT TO POWER CHECK OF EMERGENCY
LIGHTING & LETTER FOR GFI CIRCUITING.
10/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- OK BONDING & GROUNDING
- PROVIDE LETTER FROM ARCH. FOR CIRCUIT ARRANGEMENT FOR GFI OUTLET ARRANGEMENT ON ROOF. PROVIDE DISCONNECT FOR WATER HTR. RECEIVED LETTER OF TORQUE FOR SES.
08/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :
1. REVISE PLANS FOR SES EQUIP.
2. BOND BLD. STEEL, WATER, GAS
3. DAISY CHAINED BONDING AT GROUND BUSHINGS TO SMALL CONDUCTORS, USE 250-6C TABLE FOR SIZING.
08/17/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOTES:
1. HAVE ELECTRICAL CONTR, PROVIDE LETTER OF TORQUE FOR SES EQUIP. ALSO OPEN ALL EQUIP. FOR INSPECTION.
2. VERIFY ALL INTERIOR GROUNDING & BONDING
3. PROVIDE ACCESS TO ROOF.