Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03CM04472
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/06/2006 | ELECTRIC - CABLE DROP | Approved | ||
04/13/2006 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* OK U.G. SECONDARYS X-FORMER TO SES "A" & "B" |
|
03/28/2006 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* NOTE: OK DEPTH FOR PRIMARY HOWEVER, CONTRACTOR USED RED CORRIGATED FLEX DUCT - NOT ACCEPTABLE PER NEC & CITY OF TUCSON UNLESS LISTED FOR ELECTRICAL USE. TEP IS PULLING & INSTALLING CABLE PER CONTR. |
|
01/23/2006 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :*OK SECONDARY STUB UPS TO BLD. AND RUN PAST LOADING DOCKS. OK BRANCH CIRCUITS UNDER DOCK SLAB FOR SUMP PUMP |