Permit: T03CM04472

Parcel: 14027041A


Addresses:

6151 S TUCSON BL


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T03CM04472

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2006 ELECTRIC - UFER Approved IVRS - Inspection :*
12/06/2005 ELECTRIC - UFER Partial Approval IVRS - Inspection :*OK REBAR UFER 3/0 CU. CLAMPED TO REBAR-GROUND RODS NOT INSTALLED YET.
12/05/2005 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*WHEN USING 20' REBAR UFER, IT MUST BE REBAR CLOSET TO THE BOTTOM OF THE FOOTING PER 250-52 NEC. ALSO PLANS CALL FOR 2-5/8" GROUND RODS.