Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T03CM04472
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
12/06/2005 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :*OK REBAR UFER 3/0 CU. CLAMPED TO REBAR-GROUND RODS NOT INSTALLED YET. | |