Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2006 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 12/06/2005 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :*OK REBAR UFER 3/0 CU. CLAMPED TO REBAR-GROUND RODS NOT INSTALLED YET. | |
| 12/05/2005 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999*WHEN USING 20' REBAR UFER, IT MUST BE REBAR CLOSET TO THE BOTTOM OF THE FOOTING PER 250-52 NEC. ALSO PLANS CALL FOR 2-5/8" GROUND RODS. |