Permit: T03CM04453

Parcel: 13312006M

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/21/2004 MECHANICAL - INTERMEDIATE Approved
11/06/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) INSPECTED CONDENSATE DRAIN LINES. RELOCATE TO TERMINATE INTO A LAV AS PER PLANS. RECALL TO TERMINATE PIPE IN WALL 2) PROVIDE DUCT SMOKE DTECTORS AS PER PLAN OR PROVIDE A LETTTER FROM ENGINEER IF DELETING. 3) COMPLETE INSTALLATION OF EXHAUST AND SUPPLY IN RESTROOMS. RECALL FOR INSPECTION WHEN READY. OK FOR SHEET ROCK ALL OTHER AREAS