Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM04453
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
12/18/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEEDS AN APPROVED EXTENDER RING-METAL NOT APPROVED 370.20 2) FIXTURES TO BE ATTACHED TO GRID 410.16 3) NM CABLE TO BE INDEPENDENTLY SUPPORTED AS PER 300.11 AND SUPPORTED AS PER 336.18 4) DATA NOT TO BE LAYING ON GRID-PLEASE SUPPORT 5) PROTECT NM CABLE ENTERING CONDUIT 6) PLEASE OPEN GUTTER AND METER FOR INSPECTION 7) FINISH SIGN ELECTRIC POWER |