Permit: T03CM04453

Parcel: 13312006M

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM04453

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
12/18/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEEDS AN APPROVED EXTENDER RING-METAL NOT APPROVED 370.20 2) FIXTURES TO BE ATTACHED TO GRID 410.16 3) NM CABLE TO BE INDEPENDENTLY SUPPORTED AS PER 300.11 AND SUPPORTED AS PER 336.18 4) DATA NOT TO BE LAYING ON GRID-PLEASE SUPPORT 5) PROTECT NM CABLE ENTERING CONDUIT 6) PLEASE OPEN GUTTER AND METER FOR INSPECTION 7) FINISH SIGN ELECTRIC POWER